Main
range
TeSys

product name
TeSys GV2

device short name
GV2ME

device application
Motor

trip unit technology
Thermal-magnetic

Complementary
poles description
3P

network type
AC

utilisation category
AC-3 conforming to IEC 60947-4-1
Category A conforming to IEC 60947-2

network frequency
50/60 Hz conforming to IEC 60947-4-1

fixing mode
Clipped on 35 mm symmetrical DIN rail
Screwed on panel (with adaptor plate)

operating position
Any position

motor power kW
0.25 kW at 400/415 V AC 50/60 Hz
0.37 kW at 400/415 V AC 50/60 Hz
0.37 kW at 500 V AC 50/60 Hz

breaking capacity
100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2

[Ics] rated service short-circuit breaking capacity
100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2

control type
Push-button

[In] rated current
1 A

thermal protection adjustment range
0.63...1 A

magnetic tripping current
13 A

[Ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2

[Ui] rated insulation voltage
690 V AC 50/60 Hz conforming to IEC 60947-2

[Ith] conventional free air thermal current
1 A conforming to IEC 60947-4-1

[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-2

power dissipation per pole
2.5 W

mechanical durability
100000 cycles

electrical durability
100000 cycles for AC-3 at 440 V

operating rate
25 cyc/h

rated duty
Continuous conforming to IEC 60947-4-1

connections - terminals
Screw clamp terminals 2 cable(s) 1...6 mm² solid
Screw clamp terminals 2 cable(s) 1.5...6 mm² flexible without cable end
Screw clamp terminals 2 cable(s) 1...4 mm² flexible with cable end

tightening torque
1.7 N.m on screw clamp terminals

suitability for isolation
Yes conforming to IEC 60947-1

phase failure sensitivity
Yes conforming to IEC 60947-4-1

height
89 mm

width
44.5 mm

depth
78.2 mm

product weight
0.28 kg

Environment
standards
EN 60204
IEC 60947-1
IEC 60947-2
IEC 60947-4-1
NF C 63-120
NF C 63-650
NF C 79-130
UL 508
VDE 0113
VDE 0660
CSA C22.2

product certifications
ATEX
BV
CCC
CEBEC
CSA
DNV
EZU
GL
LROS (Lloyds register of shipping)
RINA
SETI
TSE
UL
EAC

protective treatment
TH

IP degree of protection
IP20 conforming to IEC 60529

IK degree of protection
IK04

ambient air temperature for operation
-20...60 °C

ambient air temperature for storage
-40...80 °C

fire resistance
960 °C conforming to IEC 60695-2-1

operating altitude
2000 m