Complementary
control circuit voltage limits
88...264 V for AC circuit 110...240 V in operation
88...242 V for DC circuit 110...220 V in operation
55 V for AC circuit 110...240 V drop-out
55 V for DC circuit 110...220 V drop-out

typical current consumption
280 mA 110...240 V AC I maximum while closing with LUB12
280 mA 110...240 V AC I maximum while closing with LUB32
280 mA 110...240 V AC I maximum while closing with LUB38
280 mA 110...220 V DC I maximum while closing with LUB12
280 mA 110...220 V DC I maximum while closing with LUB32
280 mA 110...220 V DC I maximum while closing with LUB38
35 mA 110...240 V AC I rms sealed with LUB12
25 mA 110...240 V AC I rms sealed with LUB32
25 mA 110...240 V AC I rms sealed with LUB38
35 mA 110...220 V DC I rms sealed with LUB12
25 mA 110...220 V DC I rms sealed with LUB32
25 mA 110...220 V DC I rms sealed with LUB38

heat dissipation
2 W control circuit with LUB12
3 W control circuit with LUB32
3 W control circuit with LUB38

operating time
35 ms opening with LUB12 for control circuit
35 ms opening with LUB32 for control circuit
35 ms opening with LUB38 for control circuit
50 ms closing with LUB12 control circuit
50 ms closing with LUB32 for control circuit
50 ms closing with LUB38 for control circuit

reset
Manual reset

standards
EN 60947-6-2
IEC 60947-6-2
UL 60947-4-1, with phase barrier
CSA C22.2 No 60947-4-1, with phase barrier

product certifications
range
TeSys

range of product
TeSys U

product name
TeSys U

device short name
LUCB

product or component type
Advanced control unit

device application
Motor control
Motor protection

product specific application
Basic protection and advanced functions, communication

main function available
Protection against overload and short-circuit
Earth fault protection
Protection against phase failure and phase imbalance
Manual reset

product compatibility
Power base LUB12
Power base LUB32
Power base LUB38
Power base LUB120
Power base LUB320
Power base LUB380
Reversing contactor breaker LU2B12FU
Reversing contactor breaker LU2B32FU
Reversing contactor breaker LU2B38FU

[Ue] rated operational voltage
690 V AC

network frequency
40...60 Hz

load type
3-phase motor - cooling: self-cooled

utilisation category
AC-41
AC-44
AC-43

motor power kW
1.5 kW 400...440 V AC 50/60 Hz
2.2 kW 500 V AC 50/60 Hz
3 kW 690 V AC 50/60 Hz

rated motor current adjustment range
1.25…5 A

thermal overload class
Class 10 40…60 Hz -13…158 °F (-25…70 °C) IEC 60947-6-2
Class 10 40…60 Hz -13…158 °F (-25…70 °C) UL 508

tripping threshold
14.2 x Ir +/- 20 %

phase failure sensitivity
Yes

[Uc] control circuit voltage
110...240 V AC
110...220 V DC